Hotline:0373-3519682

create and lead the future

Domestic advanced intelligent manufacturer of electronic industry

BWKG-6300

Functional features

Automatic control of reactive power compensation for power capacitor bank in 6-35kV double section bus operation system

Color LCD display in Chinese / English

Automatically identify and adapt to the operation mode of single and double variable system

Two control strategies of voltage reactive power and power factor

8-channel capacitor bank control output, 5-channel protection output

Fault input, switch position signal, external switch status, temperature alarm signal, etc

It includes the whole point record, SOE, switching record, capacitor switching frequency and practice, fault locking information, input record, etc

Over voltage protection, under voltage protection, voltage harmonic out of limit protection, refuse to operate, capacitor fault locking and other protection functions

RS485, RS232 dual port communication function, background communication function, "four remote" function

Display bus voltage, current, active power, reactive power, power factor and capacitor bank status

Display system protection, capacitor protection feedback, front switch off information and other alarm protection information

The data and bar graph show the 27th voltage, current harmonics and total distortion rate

Manual and automatic conversion function

technical parameter

Working power supply ac110v-220v, dc110v-220v

Measurement accuracy: voltage ≤± 0.5%, current ≤± 0.5%

Active power ≤± 1.0%, reactive power ≤± 1.0%, power factor ≤± 1.0%

Sampling mode two phase voltage one phase current

Sampling input voltage AC100V

Sampling input current 5A / 1A

Sampling sensitivity 60mA

Control output 8 channels, AC250V, 16A

Input: 29 channels

Alarm output 5 channels

Communication RS485, RS232

Installation mode embedded

Applicable occasions

It is suitable for 6.0kv-35.0kv double section bus high voltage distribution network