Domestic advanced intelligent manufacturer of electronic industry
BWKG-6500
Functional features
Automatic control of reactive power compensation for power capacitor bank in 6-35kV double section bus operation system
Color LCD display in Chinese / English
Automatically identify and adapt to the operation mode of single and double variable system
Two control strategies of voltage reactive power and power factor
8-channel capacitor bank control output, 5-channel protection output
Fault input, switch position signal, external switch status, temperature alarm signal, etc
It includes the whole point record, SOE, switching record, capacitor switching frequency and practice, fault locking information, input record, etc
Over voltage protection, under voltage protection, voltage harmonic out of limit protection, refuse to operate, capacitor fault locking and other protection functions
RS485, RS232 dual port communication function, background communication function, "four remote" function
Display bus voltage, current, active power, reactive power, power factor and capacitor bank status
Display system protection, capacitor protection feedback, front switch off information and other alarm protection information
The data and bar graph show the 27th voltage, current harmonics and total distortion rate
Manual and automatic conversion function
technical parameter
Working power supply ac110v-220v, dc110v-220v
Measurement accuracy: voltage ≤± 0.5%, current ≤± 0.5%
Active power ≤± 1.0%, reactive power ≤± 1.0%, power factor ≤± 1.0%
Sampling mode two phase voltage one phase current
Sampling input voltage AC100V
Sampling input current 5A / 1A
Sampling sensitivity 60mA
Control output 8 channels, AC250V, 16A
Input: 29 channels
Alarm output 5 channels
Communication RS485, RS232
Installation mode embedded
Applicable occasions
It is suitable for 6.0kv-35.0kv double section bus high voltage distribution network